DAD 141.1 Technical Manual Modbus Communication, Rev. 2.3 - Juni 2014 Page 5
The 16 bit integer data is accessed by writing one 16-bit register at index 2066.The values are:
0001h: AS Save analog parameters
0002h: CS Save calibration
0004h: WP Save general setup parameters
0010h: SS Save set-point parameters
8000h: FD Factory default
This Index is used to select Setpoint in a DAD141.
The 16 bit integer data is accessed by writing one 16-bit register at index 2067.
The values are 0 (zero) to 2 and selects the setpoint acted upon by indexes:
2068h,206Ah, 206Ch and 2070h.
This index act as the ‘n‘ parameter for the A’n‘, H’n‘, S’n‘ and P’n‘ commands
see also command description: A‘n‘ Assign action, H‘n‘ Hysteresis, S‘n‘ Setpoint, P‘n‘ Polarity
This Index is used to select Setpoint Source in a DAD141.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2068.
0 = Gross weight as setpoint source
1 = Net weight as setpoint source
2 = Peak value (Max) as setpoint source
3 = Average value as setpoint source
4 = Hold value as setpoint source
5 = Peak to Peak value as setpoint source
6 = Valley value (Min.) as setpoint source
7 = Error 4 or 5 as setpoint source
see also command description: A’n‘ (n = 0, 1, 2, 3, 4, 5, 6, 7, 8)
This Index is used to get or set Setpoint Hysteresis in a DAD141.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 206A.
see also command description: H’n‘ (n = 0, 1, 2)
This Index is used to get or set Setpoint limit in a DAD141.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 206C.
see also command description: S’n‘ (n = 0, 1, 2)
This Index is used to get or set Setpoint polaritiy in a DAD141.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2070.
The values of switch logic are 0 or 1.
see also command description: P’n‘ (n = 0, 1, 2)